polski   russkij    Google

Self-acting flow regulator valve - RQB, RQBm

Flow regulator RQB
Flow regulator RQB flanged
Flow regulator RQBm
Flow regulator RQBm screwed
Flow regulator RQB - construction
Flow regulator RQB - construction

Self-acting flow regulator valve type RQB controls set-up medium flow. Flow regulator valve type RQB is designed for water, non inflammable vapors and gases and neutral liquids. Application of this regulator is heating, industrial and power installations. The pressure regulators are capable of operating within temperatures ranging from 0 to +150°C

Description:

  • Installation on the supply or return of system.
  • Excellent control of the process over high differential pressures.
  • High quality of regulation.
  • Does not require conservation.
  • requiring no external power source.

Construction:

For ensuring stable regulation at high differential pressures, the valve-plug (4) is balanced (5). The regulator consisting of two connected components:
- a valve: valve-body (1), flow limiter(2), valve-seat (3), valve-plug (4), balanced unit (5), valve-stem (6);
- an actuator: impulse pipe (7), actuator-discs and diaphgram(8), spring (9), actuator-stem (10), adjusting nut (11), actuator case (12).

Principle of operation:

Medium flows to valve chamber (A). The flow limiter (2) determined size of the gap between chamber A and B. The control signal pass through the impulse pipe (7) from the chamber (A) to the actuator chamber (C). The value of the pressure goes by the hole in valve-plug (4) from chamber (B) to the chamber (D). The value ΔP depends on the spring tension(9). The constant difference of the pressure beetwen the chambers (C) and (D), depends on constant pressure drop ΔPm beetwen the chambers (A) and (B). The flow value is adjustable at flow limiter (2).

Installation:

Install the regulator with the actuator suspended downwards. For ensuring good work the regulator should be protect by the filter or the magnetic strainer. Install pipelines horizontally. The direction of medium flow have to correspond with the arrow on the valve body.

Installation of the flow regulators - RQB

Technical data:

Series (flanged) RQB
Diameter DN 15 20 25 32 40 50
Flow factor Kvs 3,2 5 8 12,5 20 32
Pressure PN 25 bar
Water flow m3/h
for pressure drop
0,2 Qmin 0,15 0,2 0,4 0,6 1,0 1,6
Qmax 1,3 2,0 3,2 5,0 8,0 13
0,5 Qmin 0,3 0,5 0,8 1,2 2,0 3,0
Qmax 2,3 3,5 5,6 8,8 14 23
Adjust range Dm=240 - 0,2 lub 0,5 bar
Dm=160 0,2 lub 0,5 bar -
Max. pressure diference 12 bar
Max. temprature 180 ° C
Max. pressure in
the actuator chamber
25 bar

Flanged connectors PN25, PN ISO 7005-1

series RCQoBm (srewed)
Diameter DN 15 20 25
Flow factor Kvs 3,2 4,5 6,3
Pressure PN 16 bar
Water flow m3/h
for pressure drop
0,2 Qmin 0,15 0,2 0,3
Qmax 1,3 1,8 2,6
0,5 Qmin 0,3 0,4 0,6
Qmax 2,3 3,2 4,5
Adjust range Dm=160 0,2 lub 05 bar
Max. pressure diference 12 bar
Max. temprature 150 ° C
Max. pressure in
the actuator chamber
bar

Dimensions [mm]:

Regulator screwed RQB Flow regulator screwed RQBm
Flow regulator RQB Flow regulator screwed RQBm


DN 15 20 25 32 40 50
H1 76,5 82,5 82,5 94 102 110
H2 63 66 66 - - -
H1max 215 223 226 246 248 270
H2max 172 177 177 - - -
L1 130 150 160 180 200 230
L2 75 80 85 - - -

Value range

Indicate value range 20 50 20 50
Adjust range D p [bar] 0,2 0,5 0,2 0,5
Actuator series Dm=160 Dm=240