polski   russkij    Google

Self-acting pressure differential-bleed regualtor valve - RCUB, RCUBm

Pressure differential-bleed valves RCUB
Pressure differential-bleed
valves RCUB flanged

Pressure differential-bleed valves RCUBm
Pressure differential-bleed
valves screwed RCUBm screwed

Pressure differential-bleed valves RCUB - construction
Pressure differential-bleed
valves RCUB - construction

Self-acting pressure differential-bleed valves type RCUB are designed to control set-up differential pressure in installations. Self-acting pressure differential-bleed valves are suitable for steam, non inflammable vapors and gases and neutral liquids. Adjust range of set pressure is depending on the actuator: 0,2-1,6 ; 1-2,8 ; 1- 3,5 or 2,5-7 bar. The regulators are capable of operating in temperature range from 0 to +180°C (with condensation chamber, if necessary).

Description:

  • Without energy the valve is closed
  • Excellent control of the process over high differential pressures.
  • Does not require conservation.
  • requiring no external power source.

Construction:

For ensuring stable regulation at high differential pressures, the valve-plug (3) is balanced (4). The regulator consisting of two connected units:
the valve: valve-body (1), valve-seat (2), valve-plug (3), balanced unit (4), valve-stem (5);
- the actuator: impulse pipes (6) and (7), actuator-discs and diaphragm (8), springs (9), spindle (10), adjusting nut (11), actuator-body (12).

Priciple of operation:

Medium flows to the valve chamber (A). The control signal higher pressure pass through the impulse pipe (6) to the actuator chamber (B). The control signal lower pressure pass through the ipulse pipe (7) to the actuator chamber (C). Size gap between valve-seat (2) and valve-plug (3) depending on the constant difference pressure between chamber B and C. When pressure overcomes adjusted set point, the valve-plug (3) opens. Without auxiliary energy the valve-plug (3) is closed.

Installation:

Install the regulator with the actuator suspended downwards. For ensuring good work the regulator should be protect by the filter or the magnetic strainer. Install pipelines horizontally. The direction of medium flow have to correspond with the arrow on the valve body.

Installation of the self-acting pressure differential-bleed valve RCRUB Install self-acting pressure differential-bleed valves

Technical data:

Series RCUB (flanged)
Diameter DN 15 20 25 32 40 50
Flow factor Kvs 3,2 5 8 12,5 20 32
Pressure PN 25 bar
Adjust range Dm=240 - 0,2-1,6; 1-2,8 bar
Dm=160 0,2-1,6; 1-3,5 bar -
2,5-7 bar
Max. pressure diference 12 bar
Max. temprature 180°C
Max. pressure in
the actuator chamber
20 bar

Flanged connectors PN25, PN ISO 7005-1

series RCUBm (screwed)
Diameter DN 15 20 25
Flow factor Kvs 3,2 4,5 6,3
Pressure PN 16 bar
Adjust range Dm=160 0,2-1,6; 1-3,5; 2,5-7 bar
Max. pressure diference 12 bar
Max. temprature 150°C
Max. pressure in
the actuator chamber
16 bar

Dimensions [mm]:

Pressure differential-bleed valves RCUB Pressure differential-bleed valves screwed RCUBm
Pressure differential-bleed valves RCUB Pressure differential-bleed valves screwed RCUBm


DN 15 20 25 32 40 50
H1 47,5 52,5 57,5 70 75 82,5
H2 28 31 33 - - -
H1max 336 344 347 360 362 384
H2max 318 344 333 - - -
L1 130 150 160 180 200 230
L2 75 80 85 - - -

Values range

Indicate value range 16 35 70 16 28
Adjust rangeDp [bar] 0,2...1,6 1...3,5 2,5...7 0,2...1,6 1...2,8
Actuator series Dm=160 Dm=240