Bleed valves - RCRUB, RCRUBm

Bleed valves RCRUB flanged

Bleed valves RCRUBm screwd

Bleed valves RCRUB - construction
Self-acting bleed regualtors type RCRUB are designed to control constant pressure in installations. Self-acting bleed valves are suitable for steam, non inflammable vapors and gases and neutral liquids. Application of this regulator is heating, industrial and power installations. Adjust range of set pressure is depending on the actuator: 0,2-1,6 ; 1-2,8 ; 1- 3,5 or 2,5-7 bar. The regulators are capable of operating in temperature range from 0 to +180°C (with condensation chamber, if necessary).
Description:
- The valve opens when pressure is rising.
- Excellent control of the process over high differential pressures.
- Does not require conservation.
- requiring no external power source.
Construction:
For ensuring stable regulation at high differential pressures, the
valve-plug (3) is balanced (4). The regulator consisting of two
connected components:
- executing unit (valve): valve-body (1),
valve-seat (2), valve-plug (3), balanced unit (4), valve-stem (5);
- regulating unit (actuator): impulse pipes (6), actuator discs and diaphragm (7),
springs (8), actuator-stem (9), adjusting nut (10), actuator-body
(11).
Priciple of operation:
Medium flows to valve chamber (A). Control signal pass through the impulse pipe (6) to the actuator chamber (B). The actuator chamber (C) is connected with atmosphere. Size of the gap between the valve-seat (2) and the valve-plug (3) depends on the constant difference pressure between chamber B and C. When control pressusre overcomes the set point, the valve-plug (3) opens to the moment when pressure difference between the chamber B and C will be equal to the adjusted pressure set point. Pressure value is adjusted by adjustment nut (11). Normally the valve-plug (3) is open.
Installation:
Install the regulator with the actuator suspended downwards. For ensuring good work the regulator should be protect by the filter or the magnetic strainer. Install pipelines horizontally. The direction of medium flow have to correspond with the arrow on the valve body.

Installation of the bleed valves RCRUB
Technical data:
| Series | RCRUB (flanged) | ||||||
| Diameter DN | 15 | 20 | 25 | 32 | 40 | 50 | |
| Flow factor Kvs | 3,2 | 5 | 8 | 12,5 | 20 | 32 | |
| Pressure PN | 25 bar | ||||||
| Adjust range | Dm=240 | - | 0,2-1,6; 1-2,8 bar | ||||
| Dm=160 | 0,2-1,6; 1-3,5 bar | - | |||||
| 2,5-7 bar | |||||||
| Max. pressure diference | 12 bar | ||||||
| Max. temprature | 180°C | ||||||
| Max. pressure in
the actuator chamber |
20 bar | ||||||
flanged connectors PN25, PN ISO 7005-1
| series | RCRUBm (screwed) | ||
| Diameter DN | 15 | 20 | 25 |
| Flow factor Kvs | 3,2 | 4,5 | 6,3 |
| Pressure PN | 16 bar | ||
| Adjust range Dm=160 | 0,2-1,6; 1-3,5; 2,5-7 bar | ||
| Max. pressure diference | 12 bar | ||
| Max. temprature | 150°C | ||
| Max. pressure in
the actuator chamber |
16 bar | ||
Dimensions [mm]:
![]() |
![]() |
| Pressure difference - bleed valves RCRUB flanged |
Pressure difference - bleed valves RCRUBm screwed |
| DN | 15 | 20 | 25 | 32 | 40 | 50 |
| H1 | 47,5 | 52,5 | 57,5 | 70 | 75 | 82,5 |
| H2 | 28 | 31 | 33 | - | - | - |
| H1max | 336 | 344 | 347 | 360 | 362 | 384 |
| H2max | 318 | 344 | 333 | - | - | - |
| L1 | 130 | 150 | 160 | 180 | 200 | 230 |
| L2 | 75 | 80 | 85 | - | - | - |
Values range
| Indicate value range | 16 | 35 | 70 | 16 | 28 |
| adjust rangeΔp [bar] | 0,2...1,6 | 1...3,5 | 2,5...7 | 0,2...1,6 | 1...2,8 |
| Actuator series | Dm=160 | Dm=240 | |||