polski   russkij    Google

Bleed valves - RCRUB, RCRUBm

bleed valves - RCRUB flanged
Bleed valves RCRUB flanged

 bleed valves - RCURBm
Bleed valves RCRUBm screwd

bleed valves - RCRUB - construction
Bleed valves RCRUB - construction

Self-acting bleed regualtors type RCRUB are designed to control constant pressure in installations. Self-acting bleed valves are suitable for steam, non inflammable vapors and gases and neutral liquids. Application of this regulator is heating, industrial and power installations. Adjust range of set pressure is depending on the actuator: 0,2-1,6 ; 1-2,8 ; 1- 3,5 or 2,5-7 bar. The regulators are capable of operating in temperature range from 0 to +180°C (with condensation chamber, if necessary).

Description:

  • The valve opens when pressure is rising.
  • Excellent control of the process over high differential pressures.
  • Does not require conservation.
  • requiring no external power source.

Construction:

For ensuring stable regulation at high differential pressures, the valve-plug (3) is balanced (4). The regulator consisting of two connected components:
- executing unit (valve): valve-body (1), valve-seat (2), valve-plug (3), balanced unit (4), valve-stem (5);
- regulating unit (actuator): impulse pipes (6), actuator discs and diaphragm (7), springs (8), actuator-stem (9), adjusting nut (10), actuator-body (11).

Priciple of operation:

Medium flows to valve chamber (A). Control signal pass through the impulse pipe (6) to the actuator chamber (B). The actuator chamber (C) is connected with atmosphere. Size of the gap between the valve-seat (2) and the valve-plug (3) depends on the constant difference pressure between chamber B and C. When control pressusre overcomes the set point, the valve-plug (3) opens to the moment when pressure difference between the chamber B and C will be equal to the adjusted pressure set point. Pressure value is adjusted by adjustment nut (11). Normally the valve-plug (3) is open.

Installation:

Install the regulator with the actuator suspended downwards. For ensuring good work the regulator should be protect by the filter or the magnetic strainer. Install pipelines horizontally. The direction of medium flow have to correspond with the arrow on the valve body.

  Installation
Installation of the bleed valves RCRUB

Technical data:

Series RCRUB (flanged)
Diameter DN 15 20 25 32 40 50
Flow factor Kvs 3,2 5 8 12,5 20 32
Pressure PN 25 bar
Adjust range Dm=240 - 0,2-1,6; 1-2,8 bar
Dm=160 0,2-1,6; 1-3,5 bar -
2,5-7 bar
Max. pressure diference 12 bar
Max. temprature 180°C
Max. pressure in
the actuator chamber
20 bar

flanged connectors PN25, PN ISO 7005-1

series RCRUBm (screwed)
Diameter DN 15 20 25
Flow factor Kvs 3,2 4,5 6,3
Pressure PN 16 bar
Adjust range Dm=160 0,2-1,6; 1-3,5; 2,5-7 bar
Max. pressure diference 12 bar
Max. temprature 150°C
Max. pressure in
the actuator chamber
16 bar

Dimensions [mm]:

Pressure difference  - bleed valves - RCRUB flanged Pressure difference  - bleed valves - RCRUBm screwed
Pressure difference - bleed valves
RCRUB flanged
Pressure difference - bleed valves
RCRUBm screwed


DN 15 20 25 32 40 50
H1 47,5 52,5 57,5 70 75 82,5
H2 28 31 33 - - -
H1max 336 344 347 360 362 384
H2max 318 344 333 - - -
L1 130 150 160 180 200 230
L2 75 80 85 - - -

Values range

Indicate value range 16 35 70 16 28
adjust rangeΔp [bar] 0,2...1,6 1...3,5 2,5...7 0,2...1,6 1...2,8
Actuator series Dm=160 Dm=240